tb

Oil – gas boiler

Power

114-1000kW

DESCRIPTION

• CE marked according to European directive 92/42/EEC for hot water boilers.
• Manufactured according to the new directives 2010/30/EU for energy efficiency and 2009/125/EC for energy related products.
• The tb series boilers are designed:
• With large heat exchange surface, compared to its volume, due to its water circulating façade.
• Three way fumes route, stainless steel turbulators, with increased thermal exchange.
• Cylindrical combustion chamber with perfect flame adjustment, uniform thermal absorption and silent operation.
• Modern look, with electrostatically painted covers, for damage protection.
• Insulated with high density glasswool.
• Strict quality control, of welding is performed in all the production stages. Hydraulic pressure testing is performed to assure the quality of the products.

This product is currently out of stock and unavailable.

FUELS

  • Gas

  • Oil

SPECIFICATIONS

TYPE tb 100tb 125tb 150tb 175tb 200tb 250tb 300tb 350tb 400tb 500tb 600tb 700
Output in Gas (kW) 113.9141.9172.0200.0223.9294.3347.9407.9464.0580.0695.9812.0
Real Output (kW) 105.3131.2159.0185.0212.7272.4322.1350.0422.3531.9635.4740.6
Certified efficiency rate CE 92,44**92,45**92,42**92,48**92,50**92,55**92.5892.5991.5091.7091.3091.20
Boiler Connections (in) 222 ½2 ½33334444
Length (mm) / A 1,1201,2701,3701,4951,5001,6501,7201,8201,8201,8801,9602,120
Width (mm) / B 660660720720810810880880880880880880
Height (mm) / C 1,1301,2701,2101,2101,2501,2501,3901,3901,3901,3901,3901,390
Chimney Ø (mm) 200200200200250250300300300300300300
Max Operating Temperature (°C) 959595959595959595959595
Max Operating Pressure (bar) 4.04.04.04.04.04.04.04.04.04.04.04.0
Counter pressure (mbar) 0.981.391.852.262.622.833.614.004.525.275.986.55
Operating voltage (V) 220220220220220220220220220220220220
Weight (kg) 3603784444845566007328228759561,0381,130

ACCESSORIES

  • CAO

    ANALOGUE CONTROL PANEL